Type: | Power Source Arrester |
---|---|
Structure: | Zinc Oxide Arrester |
Installation: | Parallel Arrester |
Application: | AC/DC System |
Size: | Small |
Operation Voltage: | Low Voltage |
Customization: |
---|
Suppliers with verified business licenses
Model Parameter |
RPM-100/B+C |
Maximum continuous operating voltage Uc | AC385V(50~60Hz) |
Lightning impulse current Iimp(10/350μs) | 50kA |
Nominal discharge current In (8/20μs) | 50kA |
Maximum discharge current Imax (8/20μs) | 100kA |
Protection Voltage Up | ≤2.0kV |
External protective devices | The income line should be serial connected to C character breaker with rated current no larger than 63A |
Insulation resistance Rins | >100 MΩ |
Response time | ≤100ns |
Protection degree | T1/I |
Protection mode | L-N, N-PE |
IP degree | IP20 |
Flame retardant grade of shell | V0 |
Cross- sectional area of input wire | 10~35mm2 multi strand cord |
Failure indicator | The SPD module has an indication window, which turns red when damaged |
Remote signaling | (RSC: Remote Signal Contact), NC-COM-NO Contact |
Installation wiring torque | 3Nm |
Installation mode | Using 35mm standard DIN rail |
Dimensions | 90mm×144mm×65mm(±2mm) |
Operation temperature | Normal: -5°C ~ +40°C, Limit: -40°C ~ +80°C |
Relative humidity | 30~90% (25°C) |
Atmospheric pressure | 70kPa~106kPa |
Dielectric strength | 4.2kV/1min |